PXR Command 0000 (0): 1 Write in non-volatile memory (FIX execution) - (R)Not writing-in, (W)No Request - (R)Writing in Memory, (W)Request to write in PXR Command 0000 (0): 10001 Alarm1 - Off - On 0000 (0): 10005 Alarm2 - Off - On 0000 (0): 10009 Alarm1 Output - Relay Off - Relay On 0000 (0): 10010 Alarm2 Output - Relay Off - Relay On 0000 (0): 10012 HB Alarm Output - HB Off - HB On 0000 (0): 10013 Alarm1 (same as 10001) - Off - On 0000 (0): 10014 Alarm2 (same as 10002) - Off - On 0000 (0): 10016 HB Alarm Output (same as 10012) - HB Off - HB On PXR Command 0224 (548): 30001 Process value (PV) - 0 to 10000 (0.00 to 100.00%FS - 0A79 (2681): 30002 Currently used set value (SV) - 0 to 10000 (0.00 to 100.00%FS) - F7AB (-2133): 30003 Currently used deviation (DV) - -10000 to 10000 (-100.00 to 100.00%FS) - 283C (10300): 30004 MV (output 1) - -300 to 10300 (-3.00 to 103.00%) - OUT1 FED4 (-300): 30005 MV (output 2) - -300 to 10300 (-3.00 to 103.00%) - OUT2 0001 (1): 30006 Station No. - 0 to 255 - STno 0000 (0): 30007 Alarm status - (refer to Section 7.4.) - 0000 (0): 30008 Input/main unit abnormal status - (refer to Section 7.4.) - 0000 (0): 30009 Ramp/soak current running position - 0 to 17 (refer to Section 7.4.) - STAT 0000 (0): 30010 Heater current - 0 to 5000.0 to 50.0A - CT 0000 (0): 30011 Timer 1 current count - 0 to 9999 (0 to 9999 sec) - TM-1 0000 (0): 30012 Timer 2 current count - 0 to 9999 (0 to 9999 sec) - TM-2 0000 (0): 30015 DI action status - (refer to Section 7.4.) - PXR Command 02CB (715): 31001 Process value (PV) - 0 to 10000 (0.00 to 100.00%FS - 08CA (2250): 31002 Currently used set value (SV) - 0 to 10000 (0.00 to 100.00%FS) - FA00 (-1536): 31003 Currently used deviation (DV) - -10000 to 10000 (-100.00 to 100.00%FS) - 283C (10300): 31004 MV (output 1) - -300 to 10300 (-3.00 to 103.00%) - OUT1 FED4 (-300): 31005 MV (output 2) - -300 to 10300 (-3.00 to 103.00%) - OUT2 0001 (1): 31006 Station No. - 0 to 255 - STno 0000 (0): 31007 Alarm status - (refer to Section 7.4.) - 0000 (0): 31008 Input/main unit abnormal status - (refer to Section 7.4.) - 0000 (0): 31009 Ramp/soak current running position - 0 to 17 (refer to Section 7.4.) - STAT 0000 (0): 31010 Heater current - 0 to 5000.0 to 50.0A - CT 0000 (0): 31011 Timer 1 current count - 0 to 9999 (0 to 9999 sec) - TM-1 0000 (0): 31012 Timer 2 current count - 0 to 9999 (0 to 9999 sec) - TM-2 0000 (0): 31015 DI action status - (refer to Section 7.4.) - PXR Command 0000 (0): 40001 Non-volatile memory write-in - - 0000 (0): 40002 PID/FUZZY/SELF selection - 0:PID control,1:FUZZYcontrol,2:SELF tuning control - CTrL 0A79 (2681): 40003 SV value set on face panel - 0 to 10000 - 0000 (0): 40004 Control RUN/standby - 0: Invalidate standby (RUN),1:Validate standby - STby 0000 (0): 40005 Auto tuning command - - AT 0037 (55): 40006 P - 0 to 9999 (0.0 to 999.9%) - P 035A (858): 40007 I - 0 to 32000 (0 to 3200.0) sec - i 00A5 (165): 40008 D - 0 to 9999 (0.0 to 999.9) sec - D 000E (14): 40009 Hysteresis range at two-position control - 0 to 5000 (0.00 to 50.00%FS) - HyS 000A (10): 40010 COOL - 0 to 1000 (0.0 to 100.0) - CooL 0000 (0): 40011 Dead band - -5000 to 5000 (-50.00 to +50.00) - db 015D (349): 40012 Anti-reset windup - 0 to 10000 (0.00 to 100.00%) - Ar 0000 (0): 40013 Output convergence value - -10000 to 10000 (-100.00 to 100.00%) - bAL 0000 (0): 40014 PV shift - -1000 to 1000 (-10.00 to 10.00%FS) - PVOF 0000 (0): 40015 SV offset - -5000 to 5000 (-50.00 to 50.00%FS) - SVOF 0003 (3): 40016 Input type code - 0 to 16 - P-n2 0001 (1): 40017 Temperature unit - 0:degC 1:degF - P-F 0140 (320): 40018 Input scale lower limit - -1999 to 9999 - P-SL 1D60 (7520): 40019 Input scale upper limit - -1999 to 9999 - P-SU 0001 (1): 40020 Decimal point place - 0 to 2 - P-dP 000A (10): 40022 Input filter time constant - 0 to 9000 (0.0 to 900.0 sec) - P-dF 0001 (1): 40023 RCJ yes/no - 0: Disable RCJ,1: Enable RCJ - rCJ 0000 (0): 40024 MV limit kind - 0 to 15 - PCUT FED4 (-300): 40025 Output 1 lower limit - -300 to 10300 (-3.00 to 103.00%) - PLC1 283C (10300): 40026 Output 1 upper limit - -300 to 10300 (-3.00 to 103.00%) - PHC1 FED4 (-300): 40027 Output 2 lower limit - -300 to 10300 (-3.00 to 103.00%) - PLC2 283C (10300): 40028 Output 2 upper limit - -300 to 10300 (-3.00 to 103.00%) - PHC2 0000 (0): 40031 Set value (SV) lower limit - 0 to 10000 (0.00 to 100.00%FS) - SV-L 2710 (10000): 40032 Set value (SV) upper limit - 0 to 10000 (0.00 to 100.00%FS) - SV-H 0000 (0): 40039 Heater burnout alarm set value - 0 to 500(0.0 to 50.0A) - Hb 0000 (0): 40040 Setting lock - 0 to 5 - LoC 000B (11): 40041 Alarm 1 type - 0 to 34 - ALM1 0000 (0): 40042 Alarm 2 type - 0 to 34 - ALM2 0007 (7): 40044 Alarm 1 set value or alarm 1 lower limit set value - - AL1 or A1-L FE44 (-444): 40045 Alarm 2 set value or alarm 2 lower limit set value - - AL2 or A2-L 0007 (7): 40047 Alarm 1 upper limit set value - - A1-H FE44 (-444): 40048 Alarm 2 upper limit set value - - A2-H 0000 (0): 40050 Alarm 1 hysteresis - 0 to 5000 (0.00 to 50.00%FS) - A1hy 0000 (0): 40051 Alarm 2 hysteresis - 0 to 5000 (0.00 to 50.00%FS) - A2hy 0000 (0): 40053 Alarm 1 ON-delay set value - 0 to 9999 (0 to 9999 sec) - dLy1 0000 (0): 40054 Alarm 2 ON-delay set value - 0 to 9999 (0 to 9999 sec) - dLy2 0E8A (3722): 40057 Ramp/soak No. 1 target value - 0 to 10000 (0.00 to 100.00%FS, within set value limit) - Sv-1 0000 (0): 40058 Ramp/soak No. 2 target value - 0 to 10000 (0.00 to 100.00%FS, within set value limit) - Sv-2 0000 (0): 40059 Ramp/soak No. 3 target value - 0 to 10000 (0.00 to 100.00%FS, within set value limit) - Sv-3 0000 (0): 40060 Ramp/soak No. 4 target value - 0 to 10000 (0.00 to 100.00%FS, within set value limit) - Sv-4 0000 (0): 40061 Ramp/soak No. 5 target value - 0 to 10000 (0.00 to 100.00%FS, within set value limit) - Sv-5 0000 (0): 40062 Ramp/soak No. 6 target value - 0 to 10000 (0.00 to 100.00%FS, within set value limit) - Sv-6 0000 (0): 40063 Ramp/soak No. 7 target value - 0 to 10000 (0.00 to 100.00%FS, within set value limit) - Sv-7 0000 (0): 40064 Ramp/soak No. 8 target value - 0 to 10000 (0.00 to 100.00%FS, within set value limit) - Sv-8 0000 (0): 40065 Ramp/soak No. 1 ramp time - 0 to 59999 (0 to 5999min) - TM1r 0000 (0): 40066 Ramp/soak No. 1 soak time - 0 to 5999 (0 to 5999 min) - TM1S 0000 (0): 40067 Ramp/soak No. 2 ramp time - 0 to 5999 (0 to 5999 min) - TM2r 0000 (0): 40068 Ramp/soak No. 2 soak time - 0 to 5999 (0 to 5999 min) - TM2S 0000 (0): 40069 Ramp/soak No. 3 ramp time - 0 to 5999 (0 to 5999 min) - TM3r 0000 (0): 40070 Ramp/soak No. 3 soak time - 0 to 5999 (0 to 5999 min) - TM3S 0000 (0): 40071 Ramp/soak No. 4 ramp time - 0 to 5999 (0 to 5999 min) - TM4r 0000 (0): 40072 Ramp/soak No. 4 soak time - 0 to 5999 (0 to 5999 min) - TM4S 0000 (0): 40073 Ramp/soak No. 5 ramp time - 0 to 5999 (0 to 5999 min) - TM5r 0000 (0): 40074 Ramp/soak No. 5 soak time - 0 to 5999 (0 to 5999 min) - TM5S 0000 (0): 40075 Ramp/soak No. 6 ramp time - 0 to 5999 (0 to 5999 min) - TM6r 0000 (0): 40076 Ramp/soak No. 6 soak time - 0 to 5999 (0 to 5999 min) - TM6S 0000 (0): 40077 Ramp/soak No. 7 ramp time - 0 to 5999 (0 to 5999 min) - TM7r 0000 (0): 40078 Ramp/soak No. 7 soak time - 0 to 5999 (0 to 5999 min) - TM7S 0000 (0): 40079 Ramp/soak No. 8 ramp time - 0 to 5999 (0 to 5999 min) - TM8r 0000 (0): 40080 Ramp/soak No. 8 soak time - 0 to 5999 (0 to 5999 min) - TM8S 0000 (0): 40081 Ramp/soak mode - 0 to 15 - MOD 0000 (0): 40082 Ramp/soak command - - ProG 0000 (0): 40083 Ramp/soak pattern selection - - PTn 00C2 (194): 40085 PV stable range - 0 to 10000(0.00 to 100.00%FS) - SLFb 0000 (0): 40087 Communication DI action request - (refer to section 7.4.) - 0000 (0): 40088 Control action type code - 0 to 19 - P-n1 0001 (1): 40089 Output proportional cycle (output 1) - 0: Current output type,1 to 150(1 to 150 sec):Relay, SSR drive output type - TC 001E (30): 40090 Output proportional cycle (output 2) - 1 to 150(1 to 150 sec) - TC2 0000 (0): 40092 Alarm 1 option function - 0 to 7 (binary data 000B to 111B) - A1op 0000 (0): 40093 Alarm 2 option function - 0 to 7 (binary data 000B to 111B) - A2op 0001 (1): 40095 DI1 action setting - 0 to 12 - di-1 0001 (1): 40097 Hysteresis mode setting - 0: off (main unit parameter setting) 1: on (main unit parameter setting) - ONOF 0000 (0): 40099 User zero adjustment - -5000 to 5000 (-50.00 to 50.00%FS) - ADJ0 0000 (0): 40100 User span adjustment - -5000 to 5000 (-50.00 to 50.00%FS) - ADJS 00F4 (244): 40101 DSP1 (parameter mask designation) - 0 to 255 - dSP1 00FF (255): 40102 DSP2 (parameter mask designation) - 0 to 255 - dSP2 00E0 (224): 40103 DSP3 (parameter mask designation) - 0 to 255 - dSP3 002D (45): 40104 DSP4 (parameter mask designation) - 0 to 255 - dSP4 00D4 (212): 40105 DSP5 (parameter mask designation) - 0 to 255 - dSP5 0001 (1): 40106 DSP6 (parameter mask designation) - 0 to 255 - dSP6 0000 (0): 40107 DSP7 (parameter mask designation) - 0 to 255 - dSP7 0000 (0): 40108 DSP8 (parameter mask designation) - 0 to 255 - dSP8 0080 (128): 40109 DSP9 (parameter mask designation) - 0 to 255 - dSP9 00FF (255): 40110 DSP10 (parameter mask designation) - 0 to 255 - dSP10 00FF (255): 40111 DSP11 (parameter mask designation) - 0 to 255 - dSP11 005F (95): 40112 DSP12 (parameter mask designation) - 0 to 255 - dSP12 007C (124): 40113 DSP13 (parameter mask designation) - 0 to 255 - dSP13 PXR Command 0000 (0): 41001 Non-volatile memory write-in - - 0000 (0): 41002 PID/FUZZY/SELF selection - 0:PID control,1:FUZZYcontrol,2:SELF tuning control - CTrL 08CA (2250): 41003 SV value set on face panel - 0 to 10000 - 0000 (0): 41004 Control RUN/standby - 0: Invalidate standby (RUN),1:Validate standby - STby 0000 (0): 41005 Auto tuning command - - AT 0037 (55): 41006 P - 0 to 9999 (0.0 to 999.9%) - P 035A (858): 41007 I - 0 to 32000 (0 to 3200.0) sec - i 00A5 (165): 41008 D - 0 to 9999 (0.0 to 999.9) sec - D 000A (10): 41009 Hysteresis range at two-position control - 0 to 5000 (0.00 to 50.00%FS) - HyS 000A (10): 41010 COOL - 0 to 1000 (0.0 to 100.0) - CooL 0000 (0): 41011 Dead band - -5000 to 5000 (-50.00 to +50.00) - db 00FB (251): 41012 Anti-reset windup - 0 to 10000 (0.00 to 100.00%) - Ar 0000 (0): 41013 Output convergence value - -10000 to 10000 (-100.00 to 100.00%) - bAL 0000 (0): 41014 PV shift - -1000 to 1000 (-10.00 to 10.00%FS) - PVOF 0000 (0): 41015 SV offset - -5000 to 5000 (-50.00 to 50.00%FS) - SVOF 0003 (3): 41016 Input type code - 0 to 16 - P-n2 0001 (1): 41017 Temperature unit - 0:degC 1:degF - P-F 0140 (320): 41018 Input scale lower limit - -1999 to 9999 - P-SL 1D60 (7520): 41019 Input scale upper limit - -1999 to 9999 - P-SU 0001 (1): 41020 Decimal point place - 0 to 2 - P-dP 000A (10): 41022 Input filter time constant - 0 to 9000 (0.0 to 900.0 sec) - P-dF 0001 (1): 41023 RCJ yes/no - 0: Disable RCJ,1: Enable RCJ - rCJ 0000 (0): 41024 MV limit kind - 0 to 15 - PCUT FED4 (-300): 41025 Output 1 lower limit - -300 to 10300 (-3.00 to 103.00%) - PLC1 283C (10300): 41026 Output 1 upper limit - -300 to 10300 (-3.00 to 103.00%) - PHC1 FED4 (-300): 41027 Output 2 lower limit - -300 to 10300 (-3.00 to 103.00%) - PLC2 283C (10300): 41028 Output 2 upper limit - -300 to 10300 (-3.00 to 103.00%) - PHC2 0140 (320): 41031 Set value (SV) lower limit - 0 to 10000 (0.00 to 100.00%FS) - SV-L 1D60 (7520): 41032 Set value (SV) upper limit - 0 to 10000 (0.00 to 100.00%FS) - SV-H 0000 (0): 41039 Heater burnout alarm set value - 0 to 500(0.0 to 50.0A) - Hb 0000 (0): 41040 Setting lock - 0 to 5 - LoC 000B (11): 41041 Alarm 1 type - 0 to 34 - ALM1 0000 (0): 41042 Alarm 2 type - 0 to 34 - ALM2 0005 (5): 41044 Alarm 1 set value or alarm 1 lower limit set value - - AL1 or A1-L 0000 (0): 41045 Alarm 2 set value or alarm 2 lower limit set value - - AL2 or A2-L 0005 (5): 41047 Alarm 1 upper limit set value - - A1-H 0000 (0): 41048 Alarm 2 upper limit set value - - A2-H 0000 (0): 41050 Alarm 1 hysteresis - 0 to 5000 (0.00 to 50.00%FS) - A1hy 0000 (0): 41051 Alarm 2 hysteresis - 0 to 5000 (0.00 to 50.00%FS) - A2hy 0000 (0): 41053 Alarm 1 ON-delay set value - 0 to 9999 (0 to 9999 sec) - dLy1 0000 (0): 41054 Alarm 2 ON-delay set value - 0 to 9999 (0 to 9999 sec) - dLy2 0BB8 (3000): 41057 Ramp/soak No. 1 target value - 0 to 10000 (0.00 to 100.00%FS, within set value limit) - Sv-1 0140 (320): 41058 Ramp/soak No. 2 target value - 0 to 10000 (0.00 to 100.00%FS, within set value limit) - Sv-2 0140 (320): 41059 Ramp/soak No. 3 target value - 0 to 10000 (0.00 to 100.00%FS, within set value limit) - Sv-3 0140 (320): 41060 Ramp/soak No. 4 target value - 0 to 10000 (0.00 to 100.00%FS, within set value limit) - Sv-4 0140 (320): 41061 Ramp/soak No. 5 target value - 0 to 10000 (0.00 to 100.00%FS, within set value limit) - Sv-5 0140 (320): 41062 Ramp/soak No. 6 target value - 0 to 10000 (0.00 to 100.00%FS, within set value limit) - Sv-6 0140 (320): 41063 Ramp/soak No. 7 target value - 0 to 10000 (0.00 to 100.00%FS, within set value limit) - Sv-7 0140 (320): 41064 Ramp/soak No. 8 target value - 0 to 10000 (0.00 to 100.00%FS, within set value limit) - Sv-8 0000 (0): 41065 Ramp/soak No. 1 ramp time - 0 to 59999 (0 to 5999min) - TM1r 0000 (0): 41066 Ramp/soak No. 1 soak time - 0 to 5999 (0 to 5999 min) - TM1S 0000 (0): 41067 Ramp/soak No. 2 ramp time - 0 to 5999 (0 to 5999 min) - TM2r 0000 (0): 41068 Ramp/soak No. 2 soak time - 0 to 5999 (0 to 5999 min) - TM2S 0000 (0): 41069 Ramp/soak No. 3 ramp time - 0 to 5999 (0 to 5999 min) - TM3r 0000 (0): 41070 Ramp/soak No. 3 soak time - 0 to 5999 (0 to 5999 min) - TM3S 0000 (0): 41071 Ramp/soak No. 4 ramp time - 0 to 5999 (0 to 5999 min) - TM4r 0000 (0): 41072 Ramp/soak No. 4 soak time - 0 to 5999 (0 to 5999 min) - TM4S 0000 (0): 41073 Ramp/soak No. 5 ramp time - 0 to 5999 (0 to 5999 min) - TM5r 0000 (0): 41074 Ramp/soak No. 5 soak time - 0 to 5999 (0 to 5999 min) - TM5S 0000 (0): 41075 Ramp/soak No. 6 ramp time - 0 to 5999 (0 to 5999 min) - TM6r 0000 (0): 41076 Ramp/soak No. 6 soak time - 0 to 5999 (0 to 5999 min) - TM6S 0000 (0): 41077 Ramp/soak No. 7 ramp time - 0 to 5999 (0 to 5999 min) - TM7r 0000 (0): 41078 Ramp/soak No. 7 soak time - 0 to 5999 (0 to 5999 min) - TM7S 0000 (0): 41079 Ramp/soak No. 8 ramp time - 0 to 5999 (0 to 5999 min) - TM8r 0000 (0): 41080 Ramp/soak No. 8 soak time - 0 to 5999 (0 to 5999 min) - TM8S 0000 (0): 41081 Ramp/soak mode - 0 to 15 - MOD 0000 (0): 41082 Ramp/soak command - - ProG 0000 (0): 41083 Ramp/soak pattern selection - - PTn 008C (140): 41085 PV stable range - 0 to 10000(0.00 to 100.00%FS) - SLFb 0000 (0): 41087 Communication DI action request - (refer to section 7.4.) - 0000 (0): 41088 Control action type code - 0 to 19 - P-n1 0001 (1): 41089 Output proportional cycle (output 1) - 0: Current output type,1 to 150(1 to 150 sec):Relay, SSR drive output type - TC 001E (30): 41090 Output proportional cycle (output 2) - 1 to 150(1 to 150 sec) - TC2 0000 (0): 41092 Alarm 1 option function - 0 to 7 (binary data 000B to 111B) - A1op 0000 (0): 41093 Alarm 2 option function - 0 to 7 (binary data 000B to 111B) - A2op 0001 (1): 41095 DI1 action setting - 0 to 12 - di-1 0001 (1): 41097 Hysteresis mode setting - 0: off (main unit parameter setting) 1: on (main unit parameter setting) - ONOF 0000 (0): 41099 User zero adjustment - -5000 to 5000 (-50.00 to 50.00%FS) - ADJ0 0000 (0): 41100 User span adjustment - -5000 to 5000 (-50.00 to 50.00%FS) - ADJS 00F4 (244): 41101 DSP1 (parameter mask designation) - 0 to 255 - dSP1 00FF (255): 41102 DSP2 (parameter mask designation) - 0 to 255 - dSP2 00E0 (224): 41103 DSP3 (parameter mask designation) - 0 to 255 - dSP3 002D (45): 41104 DSP4 (parameter mask designation) - 0 to 255 - dSP4 00D4 (212): 41105 DSP5 (parameter mask designation) - 0 to 255 - dSP5 0001 (1): 41106 DSP6 (parameter mask designation) - 0 to 255 - dSP6 0000 (0): 41107 DSP7 (parameter mask designation) - 0 to 255 - dSP7 0000 (0): 41108 DSP8 (parameter mask designation) - 0 to 255 - dSP8 0080 (128): 41109 DSP9 (parameter mask designation) - 0 to 255 - dSP9 00FF (255): 41110 DSP10 (parameter mask designation) - 0 to 255 - dSP10 00FF (255): 41111 DSP11 (parameter mask designation) - 0 to 255 - dSP11 005F (95): 41112 DSP12 (parameter mask designation) - 0 to 255 - dSP12 007C (124): 41113 DSP13 (parameter mask designation) - 0 to 255 - dSP13 PXR Command